      Joslyn Hi-Voltage manufactures power transmission and distribution equipment for electric utilities - reclosers
    
TriMod300 Series Vacuum Recloser
 

TriMod300 Series Vacuum Recloser - vacuum interrupter technology with a long-life solenoid operated mechanism. The new TriModä 300 Series Three Phase Vacuum Recloser raises the standard of recloser performance by incorporating state-of the-art vacuum interrupter technology with a long-life solenoid operated mechanism.

Joslyn Hi-Voltage has been a leader in solid dielectric insulation for over 35 years. The patented and field proven JOSLYTEä solid dielectric foam has been successfully used in other industry leading products such as the VerSaVacä and VarMasterä vacuum switches.
Click on photo for graphical representation
   
Check out the controls that can be used with the Trimod 300!
  Faultmaster 2500 Recloser Control
  351J Recloser Control
     
Vacuum Recloser


 
Long Operating Life
  10,000 maintenance-free operations. Recloser
Vacuum Interrupting  
  Advanced vacuum interrupter technology provides two duty cycle interruption life.
No Oil or Gas  
  Field-proven JOSLYTEä solid dielectric foam provides superior insulation and mechanical support around the vacuum interrupter and is environmentally friendly.
Long-Life Solenoid Operating Mechanism  
  Field-proven, self-lubricating design contains very few components thus increasing its reliability.
Highly Visible Mechanical Position Indicator  
  Large, reflective Open (Green) / Closed (Red) indicators are visible from ground level.
External, Easily Removable Current Transformers  
  Safety is ensured with the externally mounted current transformers (CTs) because they are surrounded with a grounded metal cover. The metal cover can easily by removed to access or replace the CTS.
Unique Modular Design  
  Identical pole design allows for the 3 poles to be mounted separately for difficult line configurations.

TriMod 300 Three Phase Vacuum Recloser Specifications
              
 Recloser  Vacuum
                         
TriModä 300 Series Three Phase Vacuum Recloser
Model
No.
Voltage Range
(kV)
Continuous
Current (AMPS)
Interrupting Current
(kA RMS Symm.)
Bil
(kV)
315-6
4 - 17.1
630 or 800
6
110
315-10
4 - 17.1
630 or 800
10
110
315-12.5
4 - 17.1
630 or 800
12.5
110
315-16
4 - 17.1
630 or 800
16
110
327-6
17 - 29.3
630 or 800
6
125
327-10
17 - 29.3
630 or 800
10
125
327-12.5
17 - 29.3
630 or 800
12.5
125
327-16
17 - 29.3
630 or 800
16
125
            
TriModä 300 Three Phase Recloser Ratings
Description
15kV
27kV
Nominal System Voltage (kV, RMS)
14.4
25
Rated Maximum Voltage (kV, RMS)
17.1
29.3
Nominal Frequency (Hz)
50 or 60
50 or 60
Number of Phases
3
3
BIL (kV)
110
125
Power Frequency Withstand - Dry (kV)
50
60
Power Frequency Withstand - Wet (kV)
45
50
Continuous Current (A RMS)
630 or 800
630 or 800
8-Hour Overload Current (A RMS)
800
800
Interrupted Current (kA RMS Symmetrical)
6, 10, 12.5, or 16
6, 10, 12.5, or 16
Making Current (kA Asym Peak)
33
33
Arc Extinction Medium
Vacuum
Vacuum
Insulating Medium
Solid High
Dielectric Material
Solid High
Dielectric Material
Mechanical Operations
10,000
10,000
Weight (lbs/kg) with standard mounting frame
275 lbs./125 kgs.
300 lbs./136 kgs.

 Recloser  Vacuum 

Ordering and Specifying Information
1 Specify TriModä 300 Vacuum Recloser by selecting voltage class, continuous current, and interrupting current rating from the ratings table.
2 Specify control cable length.
3 Specify Control:
Faultmaster 2500
351 J
   
 

Options and Accessories

Arrester mounting bracket
Substation mounting frame (9', 12', 15')
Extra creepage bushings
   
  