| Maintenance-Free | |||
| Long life of 5,000 operations. | |||
| Ease of Installation | |||
| Three phase sets can be installed quickly and easily in approximately 4 hours. | |||
| Rugged Construction | |||
| Anodized aluminum mechanism housing protects against corrosive action and sealed vacuum interrupter chamber is sealed against moisture, ultraviolet activity, and contamination - no SF-6 gas or oil is used. | |||
| Safe Interruption | |||
| Interruption is noiseless and liberates no hot exhaust or ionized gases. | |||
| Proven Performance | |||
| Installations of more than 35 years demonstrate the reliability and proven performance of the interrupter. | |||
| Air Switch Ratings Unaffected | |||
| The continuous, momentary, and impulse ratings of the switch are unaffected since the UVI is in the power circuit for a few seconds. | |||
| UVI Ratings | ||
|
Application
|
System
Voltage
(kV) |
Interrupting
Capability (Amperes) (at peak recovery voltage of 30 kV) |
|
Loop
Splitting/Parallel Switching
|
230 kV | 2000 |
|
Load
Switching
Grounded & Ungrounded Grounded Only |
25 kV 34.5 kV |
2000 |
|
Capacitor
Switching
Grounded & Ungrounded Grounded Only |
15 kV 25 kV |
800 140 |
|
Reactor
Switching
|
25 kV | 2000 |
|
Transformer
Magnetizing Switching
|
25 kV | 2000 |
|
Line
Dropping
|
25 kV 72.5 kV* |
140 15* |
|
Cable
Switching
|
25 kV 72.5 kV* |
800 15* |
| * with Voltage Limiter Attachment |
| Ordering Information | ||
| 1 | Specify air switch manufacturer | |
| 2 | Supply switch model number | |
| 3 | Specify voltage and current rating | |
| 4 | Indicate size of insulator bolt circle | |
| 5 | Describe
blade movement including clockwise or counter clockwise rotation as viewed from hinge end |
|
| 6 | Specify application, system voltage and grounding | |
|
Home | About Us | Products | Library | Contact Us Joslyn Hi-Voltage - 4000 E 116th Street, Cleveland, Ohio 44105 USA Email: T&B Contact InformationCopyright © 2001 Joslyn Hi-Voltage. All rights reserved. |