The Smartlinkä 4000 add reliable, cost-effective 2-way communications to new or existing Fisher Pierce Series 4400 capacitor controls for monitoring, control, and automation of capacitor switches. It is an integrated Remote Telemetry Module that allows for local and remote control of capacitor controls. Smartlink 4000 uses 2-way radio technology from Telemetric to communicate over digital cellular data networks. The secure web-based application supports automatic alarm or status reporting sent via email, pager, or text message. |
| Specifications | ||
| Rules-Based Processing of Digital & Analog Status Points | ||
| Alarm report on digital status point change | ||
| Analog range change rules to report analog value changes based upon 3 user defined set point values or a stair-step value | ||
| Cellular Data Network | ||
| Transmit power: 0.6 to 1.2W | ||
| Supports both 850/1900 MHz GSM/GPRS & EDGE digital packet data networks | ||
| Nationwide GPRS support via Cingular Wireless and affiliated roaming partners with a variety of application data plans | ||
| 50 Ohm SMA antenna connector | ||
| Dual-band 850/1900 MHz antenna included | ||
| Local Serial Port | ||
| RS-232 communications port for local configuration | ||
| Windows based local configuration software included with RTM | ||
| Intelligent Web Server | ||
| Data is secure and password protected | ||
| Server authentication using 128-bit encryption key validation | ||
| E-mail, text message, or pager notification options | ||
| Electrical/Environmental | ||
| 100 – 135 VAC, 60 Hz | ||
| Power provided via 120V connection to 4400 control power (front panel connector) | ||
| Surge withstand: ANSI/IEEE C37.90.1-2002, 4kV min. @ 1.2/50 μs surge | ||
| Operating temperature range: -40º to +70ºC | ||
| Enclosure Door Kit | ||
| Lexan replacement door for meter socket enclosure | ||
| NEMA 3R Rating |
| Digital Outputs to the 4400 control | ||
| 1 | Change Mode Switch Bank Reset Daily Close Count |
Remote/Local Close/Trip Clear Neutral Current Lockout |
| *Manual toggle switch on 4400 control disables all automatic and remote control functions | ||
| Digital Inputs to the 4400 control | ||
| 1 | Close Inhibit Trip Inhibit Neutral Current Status VT Wire Neutral Current Protection Anti-Hunt Last Switch Opn. Command |
Inhibit/Clear Inhibit/Clear Lockout/Clear Line-Neut/Line-Line Enabled/Disabled Enabled/Disabled Trip/Close |
| Analog Inputs from the 4400 control | ||
| 1 | - Voltage, secondary (V) - Last Delta E (V) - Current, primary (A) - Power, 3PH (kW) - VAr, 3PH (kVAr) - Power Factor (through web access) - Neutral Current (A) - Temperature deg F - Total Close Count - Close Today Count - Capacitor Control Run time (hrs) - Maximum Close Count per Day Setpoint - Operation Mode - PCC Identification Number |
- Neutral Current Sensor Type - Current Sensor Phase - Voltage Transformer Ratio - Phase Rotation - Current Direction (Forward/Reverse) - Current Transformer Ratio - Current Sensor Type - Total Angle Correction (deg) - Reverse Power Control Action - Season # - Primary Control Function - Close Setpoint - Trip Setpoint |
|